VARTA bloc range
Vb 12142...Vb 12149,
enhanced power

Application Installation
VARTA bloc batteries are designed for universal use where high safety requirements apply. They are qualified for short discharge periods at high current and for capacitive discharge over longer periods.
Their fields of application are reserve power supply systems in power stations, nuclear power stations, sub stations, UPS and industrial systems, emergency power supply systems, engine starting and energy storage in solar power systems, according to national and international standards.

All standard types of installation are permitted. Due to the improved energy density the required area for installation is reduced. When installing in battery rooms the safety provisions specified in national or international standards must be observed.

Construction Features
Positive Electrode  Rod plate with low antimony VARTA-Selenium alloy (Sb-content: 1.6%)
  • 6V/10V/12V monobloc batteries 
  • economical, universal use for all modes of discharge 
  • leakproof VARTA Safety Pole, proven in operation
  •  VARTA-Safety vent plug with flame arrestor, optional ceramic vent plug 
  • Maintenance free according to DIN about 5 years in standby parallel operation at 20°C 
  • Long service life due to VARTA rod plate technology 
  • Vent plug strip and grip slots integrated in cover, smooth sides
Negative Electrode Grid plate with lead calcium alloy
Separation Microporous separator combined with glass-mat for the positive electrode
Casing Material Modified Acrylonitrile-Butadiene-Styrene (ABS) with high impact resistance, transparent
Electrolyte   Dilute sulphuric acid, d = 1.24 kg/l
Terminal Design Leakproof safety pole design with brass insert, M8
Connectors Solid copper (20 x 3 mm), insulated, bolted type
Vent Plugs Safety plugs with flame arrestor, optional ceramic funnel plug
Charging All charging procedures in accordance with DIN 41772 and DIN 41773 float charge voltage: 2.23 V/cell ± 1% at 20°C
Temperature Range 0…+55 °C (preferred value 20 °C)
Product Standard DIN 40739
  

 

IN EN ISO 9001 CERTIFIED COMPANY

All dimensions and weights shown are subject to the usual manufacturing tolerances. Electrical values are approximate.

The right is reserved to make alterations with a view to technically improved execution without prior notice. 04.03.01a 032000 e

Type-Nr. 01004030102

*Height includes connector.

Vb 12142 – Vb 12149

Technical data
Type designation Type no. Capacity [Ah]
corresponding
to
DIN
Capacity [Ah]  Internal  resistance  short circuit current charged  Weight [kg]
C10 C5 C3 C1  Dimensions [mm]
 Final discharge voltage Uf [V/c] without connectors, batt.  elect.
1.80  1.80  1.79  1.77  [mOhm/bloc]  [A]   B H*  w. elect .
12 V monobloc batteries
Vb 12142 2719254  18  33 30.2 27.2 21.0  13.8 900 221 176 277 20.8 5.4
Vb 12143 2719279 36 50 45.3 40.8 31.5 9.1 1300 221 176 277  24.8 5.3
Vb 12144 2719295 54 66 60.4 54.4 42.0 6.9 1750 311 176 277 33.7 7.8
Vb 12146 2719319 72 99 90.6 81.6 63.0 4.6 2600 389 176 277 45.6 9.7
Vb 12147 2719335 90 116 106 95.2 73.5 3.9 3050 469 176 277 53.5 12.0
Vb 12149 2719351 108 149  136 122 94.5  3.1 3900 553 176 277 65.5 14.5