| Technical
Specification for Stationary VLA - Block - Batteries |
|
1. Application
BAE UPS - batteries are robust
and for high discharge - performances optimised lead-acid batteries. They
are particularly suitable for bridging times of a few minutes to one hour.
The main application for
BAE UPS are Uninterruptable Power Supplies (UPS) in the size of 50 to 250kVA.
Due to the low internal resistance the battery is perfectly suited to start
diesel engines for the auxiliary power supply.
|
|
|
| 2. Types, capacities,
dimensions, mass |
|
Type
|
P60min
|
P30min
|
P15min
|
P10min
|
P5min
|
Ri 1)
|
Ik 2)
|
length
L
|
width
w
|
height
max.
|
mass
3)
|
mass
4)
|
| . |
W/Z
|
W/Z
|
W/Z
|
W/Z
|
W/Z
|
mW
|
kA
|
mm
|
mm
|
mm
|
kg
|
kg
|
Ue
V / cell
|
1,75
|
1,70
|
1,65
|
1,63
|
1,60
|
. |
. |
. |
. |
. |
. |
. |
|
12V 1 UPS 100*
|
42,6
|
63,2
|
92,9
|
120,9
|
182,7
|
16,8
|
0,73
|
272
|
205
|
385
|
22
|
33
|
|
12V 2 UPS 200
|
73,6
|
110,6
|
170,8
|
219,5
|
325,7
|
8,40
|
1,46
|
272
|
205
|
385
|
30,1
|
41
|
|
12V 3 UPS 300
|
103,9
|
160,0
|
248,8
|
316,2
|
470,4
|
5,60
|
2,20
|
272
|
205
|
385
|
38,2
|
49
|
|
12V 4 UPS 400
|
136,3
|
207,4
|
325,0
|
412,9
|
613,3
|
4,20
|
2,93
|
272
|
205
|
385
|
47,3
|
58
|
|
6V 7 UPS 700
|
240,2
|
379,3
|
594,3
|
744,0
|
1051
|
1,20
|
5,13
|
272
|
205
|
385
|
37,7
|
49
|
|
6V 8 UPS 800
|
274,8
|
434,6
|
683,4
|
855,6
|
1200
|
1,05
|
5,86
|
272
|
205
|
385
|
41,9
|
53
|
|
|
12V 5 UPS 500
|
170,9
|
260,8
|
416,0
|
526,4
|
763,5
|
3,36
|
3,66
|
380
|
205
|
385
|
62,3
|
78
|
|
12V 6 UPS 600
|
205,6
|
324,0
|
505,1
|
636,1
|
904,6
|
2,80
|
4,39
|
380
|
205
|
385
|
70,5
|
86
|
|
6V 9 UPS 900
|
309,4
|
486,0
|
750,3
|
922,6
|
1308
|
0,93
|
6,59
|
380
|
205
|
385
|
51,6
|
68
|
|
6V 10 UPS 1000
|
346,2
|
533,4
|
820,8
|
1023
|
1418
|
0,84
|
7,32
|
380
|
205
|
385
|
55,7
|
72
|
|
6V 11 UPS 1100
|
385,1
|
584,8
|
887,7
|
1109
|
1525
|
0,76
|
8,05
|
380
|
205
|
385
|
58,8
|
75
|
|
6V 12 UPS 1200
|
421,9
|
632,2
|
956,4
|
1190
|
1630
|
0,70
|
8,79
|
380
|
205
|
385
|
63
|
79
|
|
1,2) internal
resistance and
short - circuit - current
from IEC 896-1
|
3) dry-charged
|
4) filled and charged
|
* 100W is the averaged
power
per plate at the 10min rate.
|
|
|
| 3. Design |
| positive electrode |
round-grid
plate with circular bars in a corrosion-resistant PbSb1,6SnSe alloy |
| negative electrode |
flat plate
with long life expander and low antimony alloy
|
| separation |
microporous
separator |
| elektrolyte |
sulphuric
acid of 1,28 kg/l,
|
| container |
high impact,
transparent SAN |
| lid |
SAN in
dark grey colour |
| blocks with blind cells |
4V, 6V,
8V, 10V |
| plugs |
labyrinth
plugs for arresting aerosol, optional ceramic plug or ceramic funnel plug
according to DIN 40740 |
| pole bushing |
100%
gas- and electrolyte-tight, sliding-pole
|
| pole |
M10, brass
insert |
| connector |
flexible
insulated copper cable, with cross-section of 35, 50, 70, 95 or 120 mm² |
| kind of protection |
IP 25
regarding DIN 40 050, touch protected according VBG 4 |
|
|
|
|
4. Charging
|
| IU - characteristic |
Imax
without limitation
U = 2,25 –2,27 V/cell between
10°C and 55°C
D U/D T = -0,004 V/K below
10°C in the monthly average |
| boost charge |
U = 2,35
to 2,40V/cell, time limited |
| charging time up to 92% |
6 h with
1,5*I10 initial current, 2.23 V/cell, 50% C10 discharged |
|
|
|
|
5. Discharge
characteristics
|
| reference temperature |
20°C |
| initial capacity |
100% |
| depth of discharge |
normally
up to 80% |
| depth of discharges |
more than
80% DOD or discharges beyond final discharge voltages (dependent on discharge
current) have to be avoided |
|
| |
| 6. Maintenance |
| every 6 month |
check
battery voltage, pilot block voltage, temperature |
| every 12 month |
take down
battery voltage, block voltage, temperature, |
|
| |
| 7. Operational data |
| operational
life |
>12
years at 20°C
|
| water refilling interval |
more than
3 years at 20°C |
| IEC 896-1 cykles |
800 |
| self-discharge |
approx.
3% per month at 20°C
|
| operational temperature |
-20°C
to 55°C
recommended 10°C to
30°C |
| ventilation requirement |
f1=0,5
(low-antimony alloy) according VDE 0510 part 2 |
| measurements according |
DIN 40
737 part 3 |
| tests according |
IEC 896-1, |
| applicable standards |
VDE 0510,
part 2 |
| transport |
no dangerous
goods during road transport |
|
| |
| Tell us your application.