| Technical
Specification for Stationary VRLA – Cells |
|
1. Application
BAE SPzV - batteries are
maintenance-free and designed for a long operational life and a high operational
safety. They are ideal for capacitive loads in hourly discharges as well
as for discharges in the 30 minute range.
BAE SPzV - batteries are
used for battery-operated power supplies in telecommunications, radio relay
stations, transformer stations, emergency light equipment (VDE 0108), UPS
equipment etc. |
|
|
| 2. Types, capacities,
dimensions, weights |
|
Type
|
C 10
|
C 5
|
C 3
|
C 2
|
C 1
|
C 1/2
|
C 1/4
|
Ri
|
Ik
|
length
|
mass
|
lead
mass
|
|
Ua
|
2,05V
|
2,03V
|
2,00V
|
1,98V
|
1,95V
|
1,86V
|
1,74V
|
. |
. |
. |
. |
. |
|
Um
|
1,95V
|
1,93V
|
1,90V
|
1,88V
|
1,85V
|
1,76V
|
1,64V
|
. |
. |
. |
|
. |
|
Ue
|
1,80V
|
1,77V
|
1,75V
|
1,74V
|
1,67V
|
1,60V
|
1,50V
|
. |
. |
. |
. |
. |
| |
Ah
|
Ah
|
Ah
|
Ah
|
Ah
|
Ah
|
Ah
|
mOhm
|
kA
|
mm
|
kg
|
kg
|
|
2 SPzV 120
|
120
|
110
|
98
|
89
|
76
|
61
|
48
|
1,70
|
1,21
|
47
|
9,0
|
6,7
|
|
3 SPzV 180
|
180
|
165
|
147
|
133,5
|
114
|
91,5
|
72
|
1,13
|
1,82
|
65
|
12,6
|
9,4
|
|
4 SPzV 240
|
240
|
220
|
196
|
178
|
152
|
122
|
96
|
0,85
|
2,42
|
83
|
16,6
|
12,4
|
|
5 SPzV 300
|
300
|
275
|
245
|
222,5
|
190
|
152,5
|
120
|
0,68
|
3,03
|
101
|
20,4
|
15,1
|
|
6 SPzV 360
|
360
|
330
|
294
|
267
|
228
|
183
|
144
|
0,57
|
3,64
|
119
|
24,1
|
17,9
|
|
7 SPzV 420
|
420
|
385
|
343
|
311,5
|
266
|
213,5
|
168
|
0,49
|
4,24
|
137
|
27,9
|
20,7
|
|
8 SPzV 480
|
480
|
440
|
392
|
356
|
304
|
244
|
192
|
0,43
|
4,85
|
155
|
32,0
|
23,7
|
|
9 SPzV 540
|
540
|
495
|
441
|
400,5
|
342
|
274,5
|
216
|
0,38
|
5,45
|
173
|
35,5
|
26,3
|
|
10 SPzV 600
|
600
|
550
|
490
|
445
|
380
|
305
|
240
|
0,34
|
6,06
|
191
|
39,4
|
29,3
|
|
|
cell width 198mm
|
cell height up to connector
650 mm
|
reference temperature
25°C
|
|
|
3 SPzV 330
|
330
|
300
|
274,5
|
246
|
201
|
156
|
111
|
0,93
|
2,16
|
65
|
26,2
|
18,8
|
|
4 SPzV 440
|
440
|
400
|
366
|
328
|
268
|
208
|
148
|
0,70
|
2,88
|
83
|
34,2
|
24,6
|
|
5 SPzV 550
|
550
|
500
|
457,5
|
410
|
335
|
260
|
185
|
0,56
|
3,60
|
101
|
42,3
|
30,5
|
|
6 SPzV 660
|
660
|
600
|
549
|
492
|
402
|
312
|
222
|
0,47
|
4,32
|
119
|
48,5
|
34,9
|
|
7 SPzV 770
|
770
|
700
|
640,5
|
574
|
469
|
364
|
259
|
0,40
|
5,04
|
137
|
56,9
|
41,0
|
|
8 SPzV 880
|
880
|
800
|
732
|
656
|
536
|
416
|
296
|
0,35
|
5,76
|
155
|
63,3
|
45,6
|
|
9 SPzV 990
|
990
|
900
|
823,5
|
738
|
603
|
468
|
333
|
0,31
|
6,48
|
173
|
73,3
|
52,8
|
|
10 SPzV 1100
|
1100
|
1000
|
915
|
820
|
670
|
520
|
370
|
0,28
|
7,20
|
191
|
80,7
|
58,1
|
|
|
cell width 198 mm
|
cell height up to connector
650 mm
|
reference temperature
25°C
|
|
| 3. Design |
| positive electrode: |
tubular
plate with corrosion-resistant PbCaSn alloy |
| negative plate: |
flate
plate with long life expander and PbCaSn alloy |
| separation: |
microporous
separator |
| elektrolyte: |
sulphuric
acid of 1,26 kg/l, fixed as GEL by fumed silica |
| container, lid: |
impact-resistant
polypropylene |
| terminal design: |
100% gas-
and electrolyte-tight, M10 brass inlay |
| connector: |
flexible
copper cable, fully insulated, steel screw, encapsulated |
| valve: |
opening
pressure 100 mbar, closing pressure 50 mbar, equipped with flame arrestor |
|
| 4.Charging |
| IU - characteristic: |
Imax
without limitation
U = 2.27 V/cell +- 1%, between
10°C and 45°C
DU/DT = -0,004 V/K below
10°C in the monthly average |
| boost charge: |
U = 2,35
to 2,40V/cell, time limited |
|
| 5. Maintenance |
| every 6 months |
check
battery voltage, pilot cell voltage, temperature |
| record battery |
and cell
voltages and temperatures |
|
| 6. Operational data |
classification
according to
EUROBAT long life, |
12+ |
| operational
life at stand by |
> 12 to
15 years at 25°C
|
| maintenance-free |
no topping
up water during life |
| IEC 896-2 cykles |
800 cycles |
| self-discharge |
approx.
3% per month at 25°C |
| operational temperature |
-20°C
to 45°C
recommended 10°C to
30°C |
| deep discharge recovery |
very
good |
| ventilation requirement |
25% (f1=0,5
and f2=0,5) according to VDE 0510 |
| applicable standards |
IEC 896-2,
VDE 0510, part 2 |
| transport |
not restricted
for air, road and sea transport |
| |
| Tell us your application.