Technical Specification for Stationary VLA - Block - Batteries

1. Application

BAE OPzS - Batteries belong to the most enduring lead acid batteries. They are suitable for stand - by operations as well as for capacity loads. They perfectly meet requirements for bridging times between 1h and more than 10h.

Fields:

Telecommunications
Microwave radio systems
Emergency lighting 
Power generation plants
Photovoltaics
 
 

 

2. Types, capacities, dimensions, mass
Type
C10
C5
C3
C1
Ri 1)
Ik 2)
length
width
height max
mass 3)
mass 4)
 .
Ah
Ah
Ah
Ah
mW
kA
mm
mm
mm
kg
kg
Ue
V/cell
1,80
1,77
1,75
1,67
 . . . . . . .
12V 1 OPzS 30
35
28,5
24,3
16,5
24
0,5
272
165
280
15
21
12V 2 OPzS 60
57
48,5
43,2
32,5
12,5
0,99
272
165
280
25,5
32
12V 1 OPzS 50
50
42,5
38,4
26,6
19,20
0,64
272
205
385
29
40
12V 2 OPzS 100
100
85
76,8
53,2
9,60
1,28
272
205
385
41
51
12V 3 OPzS 150
150
127,5
115,2
79,8
6,40
1,92
380
205
385
56
71
6V 4 OPzS 200
200
170
153,6
106,4
2,40
2,56
272
205
385
36
48
6V 5 OPzS 250
250
212,5
192
133
1,92
3,20
380
205
385
47
62
6V 6 OPzS 300
300
255
230,4
159,6
1,60
3,84
380
205
385
55
69
1, 2) internal resistance and short - circuit - current according to IEC 896-1 3) dry-charged 4) filled and charged
   
12V 1 OPzS 30 to 12V 3 OPzS 150 6V 4 OPzS 200 to 6V 6 OPzS 300
3. Design
positive electrode  tubular - plate with a woven polyester gauntlet and solid grids in a corrosion- resistant PbSb1.6SnSe - alloy
negative electrode  grid - plate in a low antimony alloy with long life expander
separation microporous separator
elektrolyte sulphuric acid with a density of 1,24 kg/l,
container  high-impact, transparent SAN (Styrol-Acryl-Nitril) 
lid  high impact SAN in dark grey colour
blocks with blind cells 4V, 6V, 8V, 10V
plugs  labyrinth plugs for arresting aerosol, optional ceramic plugs or ceramic funnel plugs
according DIN 40 740
pole - bushing  100% gas- and electrolyte-tight, sliding-pole
kind of pole  M10 brass insertion
connectors  flexible insulated copper cables, with cross-section of
35, 50, 70 or 95 mm² 
kind of protection  IP 25 regarding DIN 40050, touch protected according VBG 4.
 

4. Charging

IU - characteristic  Imax without limitation
U = 2,23 V/cell +- 1%, between 10°C and 55°C
D U/D T = -0,004 V/K below 10°C in the monthly average
boost charge  U = 2,35 to 2,40V/cell, time limited
charging time up to 90%  6h with 1,5*I10 initial current, 2.23 V/cell, 50% C10 discharged
 

5. Discharge characteristics

reference temperature 20°C
initial capacity 100%
depth of discharge (DOD)  normally up to 80%
deep discharges  more than 80% DOD or discharges beyond final discharge 
voltages (dependent on discharge current) have to be avoided
 

6. Maintenance

every 6 months  check battery voltage, pilot block voltage, temperature
every 12 months  record battery and block voltages and temperatures
check connectors
 

7. Operational data

operational life  >16 years at 20°C
water - refilling - interval  more than 3 years at 20°C
IEC 896-1 cykles 1200
self-discharge  app. 3% per month at 20°C
operational temperature  -20°C to 55°C 
recommended 10°C to 30°C
ventilation requirement  50% f1=0,5 - low antimony alloy according to VDE 0510 part 2
battery according  DIN 40 737 part 3
tests according IEC 896-1,
safety standard  VDE 0510, part 2
transport  no dangerous goods during road transport
 
Tell us your application. We support you in the selection of your battery.