| Technical
Specification for Stationary VLA - Block - Batteries |
|
1. Application
BAE OPzL - Block - Batteries
are developed for emergency light equipment according VDE 0108 and VDE
0107.
The BAE - tubular plate grants
a high operational life time in stand by operations as well as for capacitive
loads in the discharge interval from 1 to 10 hours.
The transparent containers
make the maintenance easier. |
|
|
| 2. Types, capacities,
dimensions, mass, |
|
Type
|
C10
|
C5
|
C3
|
C1
|
C1/2
|
Ri
|
IKs
|
length
|
width
|
heigth max
|
mass
|
| . |
Ah
|
Ah
|
Ah
|
Ah
|
Ah
|
mW
|
kA
|
mm
|
mm
|
mm
|
kg
|
Ue
V / cell
V / block
|
1,80
10,80
|
1,77
10,62
|
1,75
10,50
|
1,70
10,20
|
1,64
9,84
|
. |
. |
. |
. |
. |
|
|
12V 1 OPzL 30
|
38
|
32
|
28
|
19
|
14,5
|
24
|
0,50
|
272
|
165
|
280
|
21
|
|
12V 2 OPzL 60
|
67,5
|
57,5
|
51
|
37
|
28,5
|
12,5
|
0,99
|
272
|
165
|
280
|
32
|
|
12V 2 OPzL 120
|
120
|
105
|
94
|
68,5
|
54
|
8
|
1,55
|
272
|
205
|
385
|
52
|
|
12V 3 OPzL 180
|
180
|
158,5
|
140,5
|
100,5
|
77,5
|
6
|
2,00
|
380
|
205
|
385
|
72
|
|
| At final voltages of 1,83V
and 1,80V result the following capacities. |
|
Type
|
C12
|
C12
|
C8
|
C8
|
C3
|
C3
|
C1
|
C1
|
| . |
Ah
|
Ah
|
Ah
|
Ah
|
Ah
|
Ah
|
Ah
|
Ah
|
final voltage
V/cell
V / block
|
1,83
10,98
|
1,80
10,80
|
1,83
10,98
|
1,80
10,80
|
1,83
10,98
|
1,80
10,80
|
1,83
10,98
|
1,80
10,80
|
|
12V 1 OPzL 30
|
39
|
39,5
|
35,5
|
36
|
26,5
|
27,5
|
17
|
17,5
|
|
12V 2 OPzL 60
|
67
|
68
|
54,5
|
55,5
|
48
|
50
|
32
|
33,5
|
|
12V 2 OPzL 120
|
122,5
|
124
|
111,5
|
114,5
|
87
|
90,5
|
58
|
61,5
|
|
12V 3 OPzL 180
|
182
|
185
|
168
|
172
|
130
|
135
|
84,5
|
89
|
|
 |
|
12V 1 OPzL 30 bis 12V
3 OPzL180
|
|
| 3. Design |
| positive electrode |
tubular
- plate with low antimony alloy (1,6%)
|
| negative electrode |
grid -
plate in a low antimony alloy with long life expander |
| separation |
microporous
separator |
| elektrolyte |
sulphuric
acid with a density of 1,28 kg/l, |
| container |
high -
impact transparent SAN, without break - through for connectors |
| lid |
high impact
SAN in dark gray colour, connectors embedded
|
| pole bushing |
100% electrolyte
- tight |
| kind of pole |
All poles
go through the lid. The end poleshave brass inserts with a M10-thread. |
| plugs |
labyrinth
plugs, optional ceramic plugs or ceramic funnel plugs according DIN 40740 |
| connectors |
between
the cells of a block solid lead connectors covered by a plastic cap
between the blockshigh flexible
insulated cable connectors with insulated M10 - pole screws |
| kind of protection |
IP 25
regarding to DIN 40050, touch protected according VBG 4. |
voltage tap
in the middle of the battery |
M4 voltage
tap, insulated |
| blocks with blind cells |
4V, 6V,
8V, 10V |
|
|
4. Charging
|
| IU - characteristic |
Imax
without limitation
U = 2,25 V/cell +- 1% |
| boost charge |
U = 2,40V/cell,
time limited |
| charging time up to 90% |
according
VDE 0107 and VDE 0108 |
|
|
5. Discharge caracteristics
|
| reference temperature |
20°C |
| initial capacity |
100% |
| depth of discharge (DOD) |
normally
up to 80% |
| deep discharges |
discharges
beyond final discharge voltages have to be avoided. |
|
|
6. Maintenance
|
| every 6 months |
check
battery voltage, pilot block voltage, temperature |
| every 12 months |
record
battery, block voltages and temperatures |
|
|
7. Operational data
|
| operational
life |
12
years+ at 20°C |
| water - refilling - interval |
app. 3
years |
| IEC 896-1 cykles |
1000 |
| self-discharge |
app. 3%
per month at 20°C |
| operational temperature |
-20°C
to 55°C
recommended 10°C to
30°C, up to 55% allowed |
| ventilation requirement |
f1=0,5
- low antimony alloy - according to VDE 0510 part 2 |
battery measurements
according |
DIN 40
737 part 3 |
| tests according |
IEC 896-1, |
| safety standard |
VDE 0510,
part 2 |
| transport |
no dangerous
goods during road transport |
|
|
| Tell us your application.