Technical Specification for Stationary VLA - Block - Batteries

1. Application

BAE OPzL - Block - Batteries are developed for emergency light equipment according VDE 0108 and VDE 0107. 

The BAE - tubular plate grants a high operational life time in stand by operations as well as for capacitive loads in the discharge interval from 1 to 10 hours.

The transparent containers make the maintenance easier.

2. Types, capacities, dimensions, mass,
Type
C10
C5
C3
C1
C1/2
Ri
IKs
length
width
heigth max
mass
 .
Ah
Ah
Ah
Ah
Ah
mW
kA
mm
mm
mm
kg
Ue
V / cell
V / block
1,80
10,80
1,77
10,62
1,75
10,50
1,70
10,20
1,64
9,84
. . . . .  
12V 1 OPzL 30
38
32
28
19
14,5
24
0,50
272
165
280
21
12V 2 OPzL 60
67,5
57,5
51
37
28,5
12,5
0,99
272
165
280
32
12V 2 OPzL 120
120
105
94
68,5
54
8
1,55
272
205
385
52
12V 3 OPzL 180
180
158,5
140,5
100,5
77,5
6
2,00
380
205
385
72
At final voltages of 1,83V and 1,80V result the following capacities.
Type
C12
C12
C8
C8
C3
C3
C1
C1
 .
Ah
Ah
Ah
Ah
Ah
Ah
Ah
Ah
final voltage
V/cell 
V / block
1,83
10,98
1,80
10,80
1,83
10,98
1,80
10,80
1,83
10,98
1,80
10,80
1,83
10,98
1,80
10,80
12V 1 OPzL 30
39
39,5
35,5
36
26,5
27,5
17
17,5
12V 2 OPzL 60
67
68
54,5
55,5
48
50
32
33,5
12V 2 OPzL 120
122,5
124
111,5
114,5
87
90,5
58
61,5
12V 3 OPzL 180
182
185
168
172
130
135
84,5
89

 

12V 1 OPzL 30 bis 12V 3 OPzL180
3. Design
positive electrode  tubular - plate with low antimony alloy (1,6%)
 
negative electrode  grid - plate in a low antimony alloy with long life expander
separation  microporous separator
elektrolyte  sulphuric acid with a density of 1,28 kg/l,
container  high - impact transparent SAN, without break - through for connectors
lid  high impact SAN in dark gray colour, connectors embedded
 
pole bushing  100% electrolyte - tight
kind of pole  All poles go through the lid. The end poleshave brass inserts with a M10-thread.
plugs  labyrinth plugs, optional ceramic plugs or ceramic funnel plugs according DIN 40740
connectors  between the cells of a block solid lead connectors covered by a plastic cap 
between the blockshigh flexible insulated cable connectors with insulated M10 - pole screws 
kind of protection  IP 25 regarding to DIN 40050, touch protected according VBG 4.
voltage tap
in the middle of the battery
M4 voltage tap, insulated
blocks with blind cells 4V, 6V, 8V, 10V
 

4. Charging

IU - characteristic  Imax without limitation 
U = 2,25 V/cell +- 1% 
boost charge  U = 2,40V/cell, time limited
charging time up to 90%  according VDE 0107 and VDE 0108
 

5. Discharge caracteristics

reference temperature 20°C
initial capacity 100%
depth of discharge (DOD)  normally up to 80%
deep discharges  discharges beyond final discharge voltages have to be avoided.
 

6. Maintenance

every 6 months  check battery voltage, pilot block voltage, temperature
every 12 months  record battery, block voltages and temperatures
 

7. Operational data

operational life  12 years+ at 20°C
water - refilling - interval  app. 3 years 
IEC 896-1 cykles  1000
self-discharge  app. 3% per month at 20°C
operational temperature  -20°C to 55°C 
recommended 10°C to 30°C, up to 55% allowed
ventilation requirement  f1=0,5 - low antimony alloy - according to VDE 0510 part 2
battery measurements
according 
DIN 40 737 part 3
tests according IEC 896-1,
safety standard VDE 0510, part 2
transport  no dangerous goods during road transport
Tell us your application. We support you in the selection of your battery.