Technical Specification for Stationary
VLA - Block - Batteries |
| 1.
Application
BAE OGi - batteries are robust
and for high discharge - performances optimized lead-acid batteries. They
are particularly suitable for bridging times of a few minutes to one hour.
BAE OGi are used for Uninterrupted
Power Supplies (UPS), to Start Diesel Engines, and for Emergency
Power Supplies in Switching Stations of utilities, in signal systems of
railway
applications or in other stations |
|
|
|
|
| 2. Types, capacities,
dimensions, mass |
|
Type
|
|
C10
|
C3
|
C1
|
C1/2
|
C1/6
|
C1/12
|
Ri
1)
|
Ik
2)
|
length
L
|
width
B
|
height
max.
|
mass
3)
|
mass
4)
|
| . |
|
Ah
|
Ah
|
Ah
|
Ah
|
Ah
|
Ah
|
mW
|
kA
|
mm
|
mm
|
mm
|
kg
|
kg
|
|
Ue V / cell
|
|
1,80
|
1,75
|
1,70
|
1,65
|
1,65
|
1,65
|
. |
. |
. |
. |
. |
. |
. |
|
12V 1 OGi 25
|
|
38
|
26,5
|
20,5
|
16,5
|
10,8
|
8,4
|
16,8
|
0,73
|
272
|
205
|
385
|
22
|
33
|
|
12V 2 OGi 50
|
STOCK
|
54
|
45
|
35
|
28,5
|
19,6
|
15
|
8,40
|
1,46
|
272
|
205
|
385
|
30,1
|
41
|
|
12V 3 OGi 75
|
|
79
|
63
|
50
|
41
|
28,3
|
21,6
|
5,60
|
2,20
|
272
|
205
|
385
|
38,2
|
49
|
|
12V 4 OGi 100
|
STOCK
|
105
|
81
|
65
|
53,5
|
37
|
28,2
|
4,20
|
2,93
|
272
|
205
|
385
|
47,3
|
58
|
|
12V 5 OGi 125
|
|
135
|
105
|
78
|
68
|
47,1
|
35,1
|
3,36
|
3,66
|
380
|
205
|
385
|
62,3
|
78
|
|
12V 6 OGi 150
|
STOCK
|
165
|
129
|
92
|
83
|
57
|
41,6
|
2,80
|
4,39
|
380
|
205
|
385
|
70,5
|
86
|
|
6V 7 OGi 175
|
|
190
|
151
|
106
|
98
|
66,6
|
48,4
|
1,20
|
5,13
|
272
|
205
|
385
|
37,7
|
49
|
|
6V 8 OGi 200
|
STOCK
|
228
|
176
|
131
|
112
|
76,6
|
55,2
|
1,05
|
5,86
|
272
|
205
|
385
|
41,9
|
53
|
|
6V 9 OGi 225
|
|
250
|
198
|
140
|
126
|
82,6
|
60,2
|
0,93
|
6,59
|
380
|
205
|
385
|
51,6
|
68
|
|
6V 10 OGi 250
|
|
270
|
220
|
161
|
139
|
91,6
|
65,3
|
0,84
|
7,32
|
380
|
205
|
385
|
55,7
|
72
|
|
6V 11 OGi 275
|
|
300
|
243
|
182
|
152
|
99,3
|
70,2
|
0,76
|
8,05
|
380
|
205
|
385
|
58,8
|
75
|
|
6V 12 OGi 300
|
|
320
|
267
|
202
|
165
|
106
|
75
|
0,70
|
8,79
|
380
|
205
|
385
|
63
|
79
|
|
2V 24 OGi 600
|
|
684
|
528
|
427
|
336
|
230
|
165
|
0,12
|
17,57
|
205
|
272
|
385
|
41,9
|
53
|
|
2V 30 OGi 750
|
|
810
|
660
|
539
|
417
|
275
|
196
|
0,09
|
21,96
|
205
|
380
|
385
|
55,7
|
72
|
|
2V 36 OGi 900
|
|
960
|
801
|
606
|
495
|
318
|
225
|
0,08
|
26,36
|
205
|
380
|
385
|
63
|
79
|
|
| 1,2) internal resistance
and short - circuit - current from IEC 896-1 |
3) dry-charged |
4) filled and charged |
|
|
|
|
|
|
12V 1 OGi 25 to 12V
6 OGi 150
|
|
|
6V 7 OGi 175 to 6V 12
OGi 300
|
|
|
2V 24 OGi 600 to 2V
36 OGi 900
|
|
|
|
| 3. Design |
| positive
electrode |
round-grid
plate with circular bars in a corrosion-resistant PbSb1,6SnSe alloy |
| negative electrode |
flat
plate with long life expander and low antimony alloy |
| separation |
microporous
separator |
| elektrolyte |
sulphuric
acid of 1,24 kg/l, |
| container |
high impact,
transparent SAN |
| lid |
SAN in
dark gray colour |
| blocks with blind cells |
4V, 6V,
8V, 10V |
| plugs |
labyrinth
plugs for arresting aerosol, optional ceramic plug or ceramic funnel plug
according to DIN 40740 |
| pole bushing |
100% gas-
and electrolyte-tight, sliding-pole |
| pole |
M10, brass
insert |
| connector |
flexible
insulated copper cable, with cross-section of 35, 50, 70 or 95 mm² |
| kind of protection |
IP
25 regarding DIN 40050, touch protected according VBG 4 |
|
|
| 4. Charging |
| IU - characteristic |
Imax
without limitation
U = 2,23 V/cell +- 1%, between
10°C and 55°C
D U/D T = -0,004 V/K below
10°C in the monthly average |
| boost charge |
U
= 2,35 to 2,40V/cell, time limited |
| charging time up to 92% |
6h
with 1,5*I10 initial current, 2.23 V/cell, 50% C10 discharged |
|
|
| 5. Discharge characteristics |
| reference temperature |
20°C |
| initial capacity |
100% |
| depth of discharge |
normally
up to 80% |
| depth of discharges |
more than
80% DOD or discharges beyond final discharge voltages (dependent on discharge
current) have to be avoided |
|
|
| 6. Maintenance |
| every 6 month |
check
battery voltage, pilot block voltage, temperature |
| every 12 month |
take
down battery voltage, block voltage, temperature, |
|
|
| 7. Operational data |
| operational
life |
>15
years at 20°C
|
| water refilling interval |
more than
3 years at 20°C |
| IEC 896-1 cykles |
1000 |
| self-discharge |
approx.
3% per month at 20°C |
| operational temperature |
-20°C
to 55°C
recommended 10°C to
30°C |
| ventilation requirement |
f1=0,5
(low-antimony alloy) according VDE 0510 part 2 |
| measurements according
|
DIN 40
737 part 3 |
|
tests according |
IEC 896-1, |
| applicable standards |
VDE 0510,
part 2 |
| transport |
no dangerous
goods during road transport |
|
| Tell us your application.